Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
282
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
3.5.2.5
Device diagnostics
Read-only access to the device diagnostics is possible from the register memory area with
function codes 03 and 04, or the coil memory area with function codes 01 and 02.
Max. data length per access: 16 registers.
Table 3- 76 Device diagnostics
Input/holding
register
Type Discrete
input / coil
address
Identifier
Access
1)
Address high/low
0x1C00
low
Bit
0x1C00
Reserved
r
0x1C01
Reserved
r
0x1C02
Reserved
r
0x1C03
Reserved
r
0x1C04
Reserved
r
0x1C05
Reserved
r
0x1C06
Reserved
r
0x1C07
Reserved
r
high
Bit
0x1C08
Status - group fault
r
0x1C09
Status - General warning
r
0x1C0A
Status - Device
r
0x1C0B
Status - Bus
r
0x1C0C
Status - PLC/PCS
r
0x1C0D
Status - Current flowing
r
0x1C0E
Status - PE command Start_Pause pending
r
0x1C0F
Status - PE energy saving mode active
r
0x1C01
low
Bit
0x1C10
Status - On<<
r
0x1C11
Status - On<
r
0x1C12
Status - Off
r
0x1C13
Status - On>
r
0x1C14
Status - On>>
r
0x1C15
Status - Start active
r
0x1C16
Status - Interlocking time active
r
0x1C17
Status - Change-over pause active
r
high
Bit
0x1C18
Status - Runs in open direction
r
0x1C19
Status - Runs in close direction
r
0x1C1A
Status - FC
r
0x1C1B
Status - FO
r
0x1C1C
Status - TC
r
0x1C1D
Status - TO
r
0x1C1E
Status - Cold run TPF
r
0x1C1F
Status - OPO
r