Recording Channels
The sampled curves of all analog and process signals that have been created are recorded. The
constant sampling rate is 192 samples per nominal cycle. The binary changes are recorded with
a resolution of 1 kHz and a maximum of 250 changes per second and DAU.
The channels of all active DAUs are always recorded in the fault record, even if there is no limit
value violation for the channel.
Depending on the DAU different measured values are recorded:
Alternating voltage with VCDAUs and VDAUs
Alternating current with VCDAUs and CDAUs
Process signals (direct voltage/direct current) with DDAUs
Binary signals with VCDAUs, VDAUs, CDAUs, DDAUs and BDAUs
Quality tracks with VCDAUs, VDAUs, CDAUs, DDAUs and BDAUs
Tables 7-9 and 7-10 give an overview of the recorded values of the DAUs.
Table 7-9
Recorded values of the VCDAU, VDAU and CDAU depending on the input
connection
VCDAU
VDAU
CDAU
Star
connection
V
L1
, V
L2
, V
L3
, V
N
I
L1
, I
L2
, I
L3
, I
N
B
1
to B
16
V
L1-1
, V
L2-1
, V
L3-1
, V
N4
V
L1-2
, V
L2-2
, V
L3-2
, V
N8
B
1
to B
16
I
L1-1
, I
L2-1
, I
L3-1
, I
N4
I
L1-2
, I
L2-2
, I
L3-2
, I
N8
B
1
to B
16
Delta
connection
V
L12
, V
L23
, V
L31
, V
4
I
L1
, I
L2
, I
L3
, I
4
B
1
to B
16
V
L12-1
, V
L23-1
, V
L31-1
, V
4
V
L12-2
, V
L23-2
, V
L31-2
, V
8
B
1
to B
16
I
L1-1
, I
L2-1
, I
L3-1
, I
4
I
L1-2
, I
L2-2
, I
L3-2
, I
8
B
1
to B
16
Monophase
V
L1
, V
L2
, V
L3
, V
L4
I
L1
, I
L2
, I
L3
, I
L4
B
1
to B
16
V
L1
, V
L2
, V
L3
, V
L4
V
L5
, V
L6
, V
L7
, V
L8
B
1
to B
16
I
L1
, I
L2
, I
L3
, I
L4
I
L5
, I
L6
, I
L7
, I
L8
B
1
to B
16
Table 7-10
Recorded values of the DDAU and BDAU
DDAU
BDAU
D
1
, D
2
, D
3
, D
4
D
5
, D
6
, D
7
, D
8
B
1
to B
16
B
1
to B
32
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...