13
13.2 Operator and Error Messages
178
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Table 13-2 shows the allocation of LEDs 9 to 21 at delivery and describes the meaning of the
individual operator messages.
Table 13-2
Operator messages via LEDs
LED no.
Message
Definition
9
Device ready for operation
Device is ready for operation, no malfunctions
10
Supply voltage OK
Supply voltage is present
11
Battery buffer OK
Battery buffer operating without malfunctions
(optional)
12
Recording active
Is lit for the duration of a triggered fault recording
(TAR or TPR) - not with trigger cause "external
start"
13
Device synchronized
LED flashes:
a valid synchronization signal has
been detected, however, the device is not
synchronized yet;
LED lights up:
device is synchronized
14
Communication active
A communication has been set up by OSCOP P
15
Ring buffer active
Records are deleted because
≥
90 % of the
reserved memory space has been reached
16
PMU active
LED flashes:
PMU recording is active, however,
no PMU data is transferred to the PDC;
LED lights up:
PMU recording is active and PMU
data is transferred to the PDC
17
Group alarm
Device has malfunctioned
18
Normal mode
Device is in normal mode, all triggers are active
19
Lock mode
Device is in lock mode, all triggers are deactivated
20
Test mode
Device is in test mode, all triggers are active;
"Test" is entered as trigger cause
21
Manual triggers
Manual triggering of a record; "Manual" is entered
as trigger cause
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...