You can design your S7-200 program to take other actions as a result of setting the
acknowledge-notification bit. Figure D-13 shows how you can use the
acknowledge-notification bit. For this example, VB21 is assumed to be the most
significant byte of the first format word of the message.
Ladder Logic
Statement List
// Resetting the acknowledge-notification
// bit and using it to enable the next
// message
LD
V21.1
// When the operator acknowledges the
R
V21.1,1
// message, reset the bit and enable
// the next message
MOVB . . .
// Move ...
Network #
MOV_B
EN
OUT
. . .
. . .
IN
V21.1
V21.1
1
R
Figure D-13 Sample Program for Using the Acknowledge-Notification Bit
Edit-Notification Bit 2
The TD 200 sets the edit-notification bit to 1 after an edit. The CPU can read this
edit-notification bit value to recognize when an editable data value has been
changed. The program can then read and make use of the edited value.
Note
The edit-notification bit does not reset automatically when subsequent edits are
performed. If you want the TD 200 to detect and notify you of a second edit
operation, you must design your program to reset the edit-notification bit to zero.
Figure D-14 shows the placement of the edit-notification bit, located in byte 0 of
the format word.
EN- Edit-Notification
0 - Not edited
1 - Message edited
Format Word
Optional Data Value
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
MSB of
Format
LSB of
Format
MSB of
Data
LSB of
Data
0
0
0
E
P EN
A
7 6
5
4
3
2
1
0
MSB
LSB
AN
Figure D-14 Edit-Notification Bit of Byte 0 of the Format Word
TD 200 Parameters and Messages
Summary of Contents for SIMATIC TD 200
Page 22: ...1 12 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Product Overview and Installation ...
Page 84: ...A 12 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Specifications and Reference ...
Page 94: ...B 10 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Multiple CPU Configurations ...
Page 126: ...E 6 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Modifying a TD 200 Configuration ...