Diagnostic interrupt
8.3 Channel dependent diagnostic interrupts
SM331; AI 8x12 Bit Getting Started part 1: 4 -20mA
8-4
Getting Started, 11/2006, A5E00253410-02
8.3
Channel dependent diagnostic interrupts
8.3.1
There are five channel dependent diagnostic interrupts
There are five channel dependent diagnostic interrupts:
●
Configuration / programming error
●
Common mode error
●
Wire break
●
Underflow
●
Overflow
Note
Here we show you only the channel specific diagnostics for the measuring modes 2 or 4-
wire current transducers. Other measuring modes are similar but not described here.
8.3.2
Configuration / programming error
Meaning
The position of the measuring range modules does not match the measuring mode set in the
hardware configuration.
8.3.3
Common mode error
Meaning
The voltage difference U
cm
between the inputs (M-) and the common voltage potential of the
measuring circuit (M
ana
) is too high.
In our example, this error cannot occur because M
ana
is connected to M for a 2-wire
transducer (fixed potential).