Networking
5-23
Automation System S7-400 Hardware and Installation
A5E00850741-01
Optical PROFIBUS-DP Network in Partyline Topology
The optical PROFIBUS-DP network with nodes that have an integrated fiber-optic
cable interface has a
partyline topology
. The PROFIBUS nodes are
interconnected in pairs by means of Duplex fiber-optic cables.
Up to 32 PROFIBUS nodes with a fiber-optic cable interface can be
series-connected in an optical PROFIBUS-DP network. If a PROFIBUS node fails,
as a result of the partyline topology none of the downstream DP slaves can be
accessed by the DP master.
Programming
device/PC/OP
PROFIBUS
cable
Optical PROFIBUS-DP
Distances between 2
nodes:
Plastic fiber-optic cable up
to 50 m
PCF fiber-optic cable up to
300 m
OBT
OBT
S7-400 with IM 467 FO
ET 200M with
IM 153-2 FO
Other field devices without
fiber-optic cable interface
Other
nodes
Figure 5-13 Optical PROFIBUS-DP Network with Nodes that have an Integrated Fiber-Optic Cable
Interface
Transmission Rate
The following transmission rates are possible when the optical PROFIBUS-DP
network is operated with a partyline topology:
•
9.6 kbps
•
19.2 kbps
•
45.45 kbps
•
93.75 kbps
•
187.5 kbps
•
500 kbps
•
1.5 Mbps
•
12 Mbps
Summary of Contents for Simatic S7-400
Page 6: ...Preface vi Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Page 52: ...Installing the S7 400 2 36 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Page 60: ...Addressing the S7 400 3 8 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Page 128: ...Networking 5 30 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Page 148: ...Commissioning 6 20 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Page 228: ...Index Index 4 Automation System S7 400 Hardware and Installation A5E00850741 01 ...