Event class 9 (09H):
"Response message frame received from interconnection partner with errors or error message frame"
Event no.
Event text
Remedy
(09)08H
Only for RK 512:
Partner detects synchronous error:
Message frame sequence error.
This error occurs at the restart of your own
programmable controller or of the partner. This
represents normal system startup behavior. You do
not need to correct anything. The error is also
conceivable during operation as a consequence of
previous errors. Otherwise, you can assume a
malfunction of the partner device.
(09)09H
Only for RK 512:
DB/DX locked at the partner by coordination flag
In the partner program: Reset the coordination
memory after the last transmission data was
processed!
In the program: Repeat the request!
(09)0AH
Only for RK 512:
Errors in message frame header that are detected
by the partner: 3rd command byte in header is
incorrect
Check whether the error was caused by faults or by
malfunction of the partner station. Prove this using
an interface test device interconnected in the data
link.
(09)0BH
Only for RK 512:
Error in message frame header: 1. or 4th
command byte in header is incorrect
Check whether the error was caused by faults or by
malfunction of the partner station. Prove this using
an interface test device interconnected in the data
link.
(09)0CH
Only for RK 512:
Partner detects incorrect message frame length
(total length).
Check whether the error was caused by faults or by
malfunction of the partner station. Prove this using
an interface test device interconnected in the data
link.
(09)0DH
Only for RK 512:
Partner was not yet restarted.
Restart the partner programmable controller or set
the mode selector switch on the CP to RUN.
(09)0EH
Only for RK 512:
Unknown error number received in the response
message frame.
Check whether the error was caused by faults or by
malfunction of the partner station. Prove this using
an interface test device interconnected in the data
link.