553BTechnical specifications
A.7 Thermocouple and RTD signal modules (SMs)
S7-1200 Programmable controller
714
System Manual, 11/2011, A5E02486680-05
Representation of analog values for Thermocouple Type J
A representation of the analog values of thermocouples type J is shown in the table below.
Table A- 99 Representation of analog values of thermocouples type J
Units
Units
Type J in °C
Decimal
Hexadecimal
Type J in °F
Decimal
Hexadecimal
Range
> 1450.0
32767
7FFF
> 2642.0
32767
7FFF
Overflow
1450.0
:
1200.1
14500
:
12001
38A4
:
2EE1
2642.0
:
2192.2
26420
:
21922
6734
:
55A2
Overrange
1200.0
:
-150.0
12000
:
-1500
2EE0
:
FA24
2192.0
:
-238.0
21920
:
-2380
55A0
:
F6B4
Rated range
< -150.0
-32768
8000
< -238.0
-32768
8000
Underflow
1
1
Faulty wiring (for example, polarity reversal, or open inputs) or sensor error in the negative
range (for example, wrong type of thermocouple) may cause the thermocouple module to
signal underflow.
A.7.2
SM 1231 RTD
SM 1231 RTD specifications
Table A- 100 General specifications
Technical data
SM 1231 AI 4 x RTD x 16 bit
SM 1231 AI 8 x RTD x 16 bit
Order number
6ES7 231-5PD30-0XB0
6ES7 231-5PF30-0XB0
Dimensions W x H x D (mm)
45 x 100 x 75
70 x 100 x 75
Weight
220 grams
270 grams
Power dissipation
1.5 W
1.5 W
Current consumption (SM Bus)
80 mA
90 mA
Current consumption (24 VDC)
1
40 mA
40 mA
1
20.4 to 28.8 VDC (Class 2, Limited Power, or sensor power from CPU)
Table A- 101 Analog inputs
Technical data
SM 1231 AI 4 x RTD x 16 bit
SM 1231 AI 8 x RTD x16 bit
Number of inputs
4
8
Type
Module referenced RTD and Ω
Module referenced RTD and Ω