Nominal size
Cable gland for Ex e II
TypeHSK-M
Cable gland for Ex e / Ex d IIC
Type ADE 1F, ADE 4F R... / B...
Union nut
Connection thread
Union nut / connection
thread
Union nut / connection
thread
M20 x 1.5
5
7
20
23
M25 x 1.5
7
10
30
29
M32 x 1.5
7
10
55
33
M40 x 1.5
7
10
75
41
M50 x 1.5
7
10
100
50
M63 x 1.5
7
10
135
75
M75 x 1.5
-
-
175
100
6.2.13
Connecting aluminum conductors
If you are using aluminum conductors, comply in addition with the following:
● Use only cable lugs that are suitable for connecting aluminum conductors.
● Immediately before inserting the aluminum conductor, remove the oxide layer from the
contact areas on the conductor and/or the mating piece, by brushing or filing.
● Then grease the contact areas immediately using neutral vaseline in order to avoid re-
oxidation.
NOTICE
Aluminum flow due to contact pressure
Aluminum flows following installation due to the contact pressure. The connection with
the clamping nuts can loosen as a result. The contact resistance would increase and the
current-carrying impeded; as a consequence the terminal box and the surrounding
components could burn. This could result in material damage to the machine or even in
total failure, which could in turn lead to indirect material damage to the system.
Retighten the clamping nuts after approximately 24 hours and then again after
approximately four weeks. Make sure that the terminals are de-energized before you
tighten the nuts.
6.2.14
O-ring seal
If O-ring seals are present, you should check that they are in perfect condition and that the O-
ring seals are properly seated in the grooves between the components. Replace any damaged
O-ring seals.
O-ring seals can be present on the following components, for instance:
● Tapers
● Cable glands
● Bearing seals
Electrical connection
6.2 Connecting
LOHER CHEMSTAR 1PS5
Operating Instructions 03/2014
63
Summary of Contents for SIMATIC S5 1P 243
Page 2: ...11 03 2014 02 49 V4 00 ...
Page 12: ...Introduction LOHER CHEMSTAR 1PS5 12 Operating Instructions 03 2014 ...
Page 20: ...Safety notes 2 11 Ventilation LOHER CHEMSTAR 1PS5 20 Operating Instructions 03 2014 ...
Page 66: ...Electrical connection 6 2 Connecting LOHER CHEMSTAR 1PS5 66 Operating Instructions 03 2014 ...
Page 124: ...Disposal 11 4 Disposal of components LOHER CHEMSTAR 1PS5 124 Operating Instructions 03 2014 ...
Page 136: ...Quality documents C 4 Data LOHER CHEMSTAR 1PS5 136 Operating Instructions 03 2014 ...
Page 140: ...Index LOHER CHEMSTAR 1PS5 140 Operating Instructions 03 2014 ...
Page 141: ...AC EC Declaration of Conformity U161 AB EC Declaration of Conformity U163 AA R No 20000h U165 ...