For a slave that has been newly introduced into a segment to be polled by the master in the
future, the master sends a "Hello frame" at the beginning of each cycle. Communication is
then paused according to the "Hello Phase" time so that slaves that are not connected to the
master yet have time to respond.
If entering and leaving the communication segment is not an application (for example, in
plants with only one segment), you can also set the "Hello Phase" to "0 ms". The cycle time
is reduced by the duration of the "Hello Phase" in this case.
Visibility of the parameters
The "Hello-Phase" timer and the timeout values are parameters that can only be configured
in the Master operating mode.
Dependencies
The "Hello Phase" and all timeout values must be shorter than the "Blacklist Timer". This is
checked by the system and displayed as error, if necessary.