Alarms
5-2
SIMATIC PCS 7 OSx 4.1.2 Operator
5.1
Alarm Notification and Acknowledgment
When a process upset occurs while the system is in the Operate state, the
operator receives both a visual and audible indication of the alarm at the
OSx station. A dual triangle symbol, an alarm icon, appears in the lower
right part of the screen, as shown in
. At the same time, an
audible alarm sounds.
The color coding of the alarm icon and the tonal quality of the audible alarm
indicate alarm priority.
shows the default alarm priorities and the
abbreviations for each. Within the PCS 7 OSx system, critical is the highest
priority alarm, and maintenance is the lowest priority alarm.
Table 5-1
Alarm Priority Indicators
Alarm Priority
Color Code
Alarm Tone
Critical (C)
Black on Red
Rapid; high-pitched
Warning (W)
Black on Yellow
Slow; low-pitched
Information (I)
White on Blue
None
Maintenance (M)
Printed Only
None
File Controls Startup Data Tags
Editors Help
Figure 5-1
Location of Alarm Icon
Operator Checks
Alarm Group
Importance List
Operator
Silences
Alarm
Operator
Notified
of Alarm
Next Task:
Operator Checks
Alarm Summary
Next Task:
Operator
Acknowledges
Alarm
Next Task:
Current Task:
Next Task:
Summary of Contents for SIMATIC PCS 7 OSx
Page 6: ......
Page 12: ...viii Contents Appendix A Advanced Operator Tasks A 1 Index Index 1 ...
Page 22: ...Preface xviii SIMATIC PCS 7 OSx 4 1 2 Operator ...
Page 102: ...OSx Station Control 2 20 SIMATIC PCS 7 OSx 4 1 2 Operator ...
Page 124: ...Trends 4 12 SIMATIC PCS 7 OSx 4 1 2 Operator ...
Page 172: ...Action Requests 7 20 SIMATIC PCS 7 OSx 4 1 2 Operator ...
Page 192: ...Batch 8 20 SIMATIC PCS 7 OSx 4 1 2 Operator ...
Page 205: ...Reports 9 13 SIMATIC PCS 7 OSx 4 1 2 Operator Figure 9 7 Entering Time Schedule Data ...
Page 222: ...Navigation A 2 SIMATIC PCS 7 OSx 4 1 2 Operator ...