Connecting up
6.3 Power supply
SCALANCE XM-400
Operating Instructions, 09/2018, C79000-G8976-C306-08
59
Information on the power supply
●
The "L1" and "L2" LEDs indicate the current range of the power supply, see the section
"LEDs "L1" and "L2" (Page 35)".
●
The power supply is connected using a 4-pin plug-in terminal block (spring-loaded
terminal). The terminal block ships with the device and can also be ordered as a spare
part.
●
The power supply can be connected redundantly. Both inputs are isolated. There is no
distribution of load. When a redundant power supply is used, the power supply unit with
the higher output voltage supplies the SCALANCE XM-400 alone.
●
The power supply is connected over a high resistance with the enclosure to allow an
ungrounded set up. The two power inputs are non-floating.
●
To wire up the power connector, use a copper cable of category 18-12 AWG or cable with
a cross-section of 0.75 to 2.5 mm².
Position and assignment
Figure 6-1
Position of the power supply on the SCALANCE XM-400 and the assignment of the
terminal block
Contact
Assignment
L1+
24 VDC
M1
Ground
M2
Ground
L2+
24 VDC