Certification
6.2 EMC and Environmental Type Tests
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Description
Test Levels
Enclosure Contact
±2 kV
±8 kV
ESD
Enclosure Air
±15 kV
Radiated RFI
Enclosure Ports
35 V/m
Signal Ports
4 kV @ 2.5 kHz
DC Power Ports
4 kV
AC Power Ports
4 kV
Fast Transient
Earth Ground Ports
4 kV
Signal Ports
2.5 kV Common Mode @ 1 MHz
DC Power Ports
2.5 kV Common
1 kV differential mode @ 1 MHz
Oscillatory
AC Power Ports
2.5 kV Common
1 kV differential mode @ 1 MHz
Signal Ports
5 kV (Fail-Safe Relay Output)
DC Power Ports
5 kV
HV Impulse
AC Power Ports
5 kV
Signal Ports
2 kV
DC Power Ports
2 kV
Dielectric
Strength
AC Power Ports
2 kV
Damped
Oscillatory
Magnetic Field
Enclosure Ports
100 A/m
Environmental Type Tests
Test
Description
Test Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40 °F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185 °F), 16 Hours
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
Test Db
95% (Non-Condensing),
55 °C (131 °F), 6 Cycles
IEC 60068-2-6
IEC 60255-21-1
Vibration
2g @ 10-150 Hz, 2 hours per axis
IEC 60068-2-27
IEC 60255-21-2
Shock
30 g @ 11 ms
44
RUGGEDCOM RSG2300
Installation Manual, 04/2022, C79000-G8976-1046-18