Technical Specifications
5
This section details the specifications and operating conditions of the device.
5.1
Power Supply Specifications
Power
Supply Type
Minimum
Input
Maximum
Input
Internal
Fuse Rating
Isolation
Maximum
Power
Consumption
12–24 VDC
10 VDC
36 VDC
24 VDC
18 VDC
36 VDC
48 VDC
36 VDC
72 VDC
1.5 kVDC
HI (125/250
VDC)
88 VDC
300 VDC
4 kVAC
HI (110/230
85 VAC
265 VAC
3.15A (T)
5.5 kVDC
10 W
(T) denotes time-delay fuse.
This is the same power supply for both AC and DC.
5.2
Failsafe Alarm Relay Specifications
Maximum Switching Voltage
Rated Switching Current
Isolation
30 VDC
2 A, 60 W
125 VDC
0.24 A, 30 W
125 VAC
0.5 A, 62.5 W
220 VDC
0.24 A, 60 W
250 VAC
0.25 A, 62.5 W
1500 V
rms
for 1 minute
5.3
Copper Ethernet Port Specifications
Data Port
10/100 Mbps
Media
CAT-5 UTP or STP
Distance
100 m (328 ft)
Connector Type
RJ45 or M12
RUGGEDCOM RS969
Installation Manual, 01/2021, C79000-G8976-1038-03
25