Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
DC Power
ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
IEC
61000-4-29
30% for 1 period,
60% for 50 periods
IEC
61000-4-11
Voltage Dips and Interrupts
AC Power
ports
100% for 5 periods,
100% for 50 periods
Signal ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
DC Power
ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
IEC
61000-4-12
Damped Oscillatory
AC Power
ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
Signal ports
30 V Continuous,
300 V for 1 s
4
IEC
61000-4-16
Mains Frequency Voltage
DC Power
ports
30 V Continuous,
300 V for 1 s
4
IEC
61000-4-17
Ripple on DC Power Supply
DC Power
ports
10%
3
Signal ports
2 kVAC (Fail-
Safe Relay output)
DC Power
ports
1.5 kVDC
Dielectric Strength
AC Power
ports
2 kVDC
Signal ports
5 kV (Fail-Safe
Relay Output)
DC Power
ports
5 kV
IEC 60255-5
HV Impulse
AC Power
ports
5 kV
IEEE 1613 (C37.90.x) EMC Immunity Type Tests
Note
RUGGEDCOM products meet Class 1 requirements for copper Ethernet
configurations and Class 2 for fiber Ethernet configurations. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
IEEE Test
IEEE 1613
Clause
Description
Test Levels
Enclosure Contact
±8 kV
C37.90.3
9
ESD
Enclosure Air
±15 kV
C37.90.2
8
Radiated RFI
Enclosure ports
35 V/m
Signal ports
±4 kV @ 2.5 kHz
C37.90.1
7
Fast
Transient
DC Power ports
±4 kV
30
RUGGEDCOM RS8000A