Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
Earth
ground ports
± 4 kV
4
Signal ports
2 kV
3
DC Power
ports
± 2 kV line-to-earth,
± 1 kV line-to-line
3
IEC
61000-4-5
Surge
AC Power
ports
± 4 kV line-to-earth,
± 2 kV line-to-line
4
Signal ports
10 V
3
DC Power
ports
10 V
3
AC Power
ports
10 V
3
IEC
61000-4-6
Induced (Conducted) RFI
Earth
ground ports
10 V
3
100 A/m
Note
IEC
61000-4-8
Magnetic Field
Enclosure
ports
1000 A/m for 3 s
5
DC Power
ports
30% for 0.1 s,
100% for 0.05 s
IEC
61000-4-29
IEC
61000-4-11
Voltage Dips and Interrupts
AC Power
ports
30% for 1 period,
100% for 5 periods,
100% for 250 periods
Signal ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
DC Power
ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
IEC
61000-4-12
Damped Oscillatory
AC Power
ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
Signal ports
30 V Continuous,
300 V for 1 s
4
IEC
61000-4-16
Mains Frequency Voltage
DC Power
ports
30 V Continuous,
300 V for 1 s
4
IEC
61000-4-17
Ripple on DC Power Supply
DC Power
ports
± 15%
4
Signal ports
2 kVAC (Fail-
Safe Relay output)
DC Power
ports
1.5 kV
Dielectric Strength
AC Power
ports
2 kV
Signal ports
5 kV (Fail-Safe
Relay Output)
DC Power
ports
5 kV
IEC 60255-5
HV Impulse
AC Power
ports
5 kV
Siemens specified severity level.
RUGGEDCOM RS416
Installation Manual, 04/2021, C79000-G8976-1018-10