Certification
5.1.7 RoHS
5.1.7
RoHS
This device is declared by Siemens AG to meet the requirements of the following
RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain
hazardous substances in electrical and electronic equipment:
•
China RoHS 2
Administrative Measure on the Control of Pollution Caused by Electronic
Information Products
A copy of the Material Declaration is available online at
support.industry.siemens.com/cs/ww/en/view/109738831
5.1.8
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
•
IEC 61850-3
Communications Networks and Systems for Power Utility Automation – Part 3:
General Requirements
•
NEMA TS-2
Traffic Controller Assemblies with NTCIP Requirements
5.2
EMC and Environmental Type Tests
The RUGGEDCOM RMC has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
Description
Test Levels
Severity
Levels
Enclosure
Contact
± 8 kV
4
IEC
61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC
61000-4-3
Radiated RFI
Enclosure
Ports
20 V/m
Note
Signal Ports
± 4 kV @ 2.5 kHz
Note
DC Power
Ports
± 4 kV
4
AC Power
Ports
± 4 kV
4
IEC
61000-4-4
Burst (Fast Transient)
Earth
Ground Ports
± 4 kV
4
RUGGEDCOM RMC
Installation Manual, 04/2021, C79000-G8976-1006-10
25