WARNING
The device may only be operated in an environment of contamination class 1 or 2 (see EN/IEC
60664-1, GB/T 16935.1).
WARNING
When used in hazardous environments corresponding to Class I, Division 2 or Class I, Zone 2,
the device must be installed in a cabinet or a suitable enclosure.
Notes for use in hazardous locations according to ATEX, IECEx, UKEX and CCC Ex
If you use the device under ATEX, IECEx, UKEX or CCC Ex conditions you must also keep to the
following safety instructions in addition to the general safety instructions for protection against
explosion:
WARNING
To comply with EU Directive 2014/34 EU (ATEX 114), UK-Regulation SI 2016/1107 or the
conditions of IECEx or CCC-Ex, the housing or cabinet must meet the requirements of at least
IP54 (according to EN/IEC 60529, GB/T 4208) in compliance with EN IEC/IEC 60079‑7, GB
3836.8.
WARNING
Requirements for the cabinet/enclosure
The fiber-optic bus connections labeled SCALANCE MM400 (see type plate) may also be led
through a hazardous area zone1 (see chapterApprovals (Page 39), section "ATEX").
WARNING
If the temperature of the cable or housing socket exceeds 70 °C or the branching point of
conductors exceeds 80 °C, special precautions must be taken. If the equipment is operated in
an air ambient in excess of 50 °C to 60 °C, only use cables with a permissible operating
temperature of at least 85 °C.
installing and removing
5.1 Safety notices for installation
MM900 media modules for SCALANCE XR-500M
18
Compact Operating Instructions, 04/2022, A5E03275846-05