32
IE/AS
−
INTERFACE LINK PN IO
as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000
−
G8976
−
C216
−
03
2 Procedure − Configuration
This chapter...
This chapter provides you with an overview of the steps and procedures involved
in configuring the IE/AS-i LINK. You will learn the basic steps leading to
commissioning and the configuration options made available to you by the IE/AS-i
LINK.
2.1
What to do − an Overview
Preparations up to Commissioning
Before putting the system into operation, the following independent steps must first
be worked through:
Write your user
program with analog
value access for the
PROFINET IO
controller
−
Configure the
PROFINET IO controller
with IE/AS-i Link as
PROFINET IO device and
AS-i master
−
Configure a PROFINET IO
system in HW Config of
STEP 7
Putting into operation
−
Write your user
program with binary
value access for the
PROFINET IO
controller
−
For example, create a program
for an S7 CPU with a PROFINET IO
interface in LAD/FBD/STL
Connecting up the
IE/AS-i Link and the slaves
incl. address assignment and,
if required, adopting the actual
as the expected configuration
−