Command Interface
5-11
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
Command Status
Whether or not the job was executed correctly or errors occurred is signaled in the
command status of the response buffer in byte 1.
Table 5-6
Value
Meaning
00
H
Job completed without error
81
H
The AS-i slave address is incorrect
82
H
The AS-i slave is not activated (not in LAS).
83
H
Error on AS-Interface.
84
H
Command not permitted in the current status of the AS-i master.
85
H
An AS-i slave with address 0 exists.
86
H
The AS-i slave has illegal configuration data (I/O or ID codes).
A1
H
The addressed AS-i slave was not found on the AS-Interface.
A2
H
An AS-i slave with address 0 exists.
A3
H
An AS-i slave with the new address already exists on the AS-Interface.
A4
H
The AS-i slave address cannot be deleted.
A5
H
The AS-i slave address cannot be set.
A6
H
The AS-i slave address cannot be stored permanently.
A7
H
Error reading the extended ID1 code.
A8
H
The target address is not plausible (for example a B slave address was
used for a standard slave).
B1
H
A length error has occurred transferring a string according to profile 7.4.
B2
H
A protocol error has occurred transferring a string according to profile
7.4.
F8
H
The job number or the job parameter is unknown.
F9
H
The AS-i master has detected an EEPROM error.
Summary of Contents for SIMATIC NET CP 243-2
Page 4: ...Preface ii SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...
Page 8: ...Contents vi SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...
Page 128: ...Command Interface 5 60 SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...
Page 142: ...Notes on the CE Mark C 2 SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...
Page 148: ...Glossary Glossary 4 SIMATIC NET CP 243 2 AS i Master C79000 G8976 C142 02 ...