Diagnostics
5.2 Error messages of the CP 243-1
CP 243-1
114
Operating Instructions, 03/2012, C79000-G8976-C244-02
5.2.2
Error messages in word format
Error word
Description
Reaction/remedy
Transfer mechanism
Hex
dec
Byte offset in the
SM area
Return value
(ETHx_)
16#0001
1
Timeout on the S7 bus
Automatic restart
20, 21
_CTRL
16#000D
13
All data transfers are aborted
because a new configuration
was triggered by the user
program.
Restart of the system
20, 21
_CTRL
16#0030
48
The configuration could not
be called up by the CPU
within the time specified.
Automatic restart
20, 21
_CTRL
16#0031
49
No CDB configuration with
correct syntax found in the
memory of the S7-200 CPU
Check the configuration 20, 21
_CTRL
16#0032
50
The CRC checksum of the
configuration data (CDB,
NDB, IDB) is incorrect
Reconfiguration of the
CP 243-1 with STEP 7
Micro/WIN 32
Check the user program
to find out whether
configuration data was
accidentally overwritten
20, 21
_CTRL
16#0033
51
The configuration data for the
CP 243-1 contains errors or is
not stored correctly.
Reconfiguration of the
CP 243-1 with STEP 7
Micro/WIN 32
20, 21
_CTRL
16#0034
52
The pointer to the CDB is
wrong or no CDB is loaded
Make sure that the
ETHx_CTRL subroutine
generated by the wizard
is called at the
beginning of the user
program.
20, 21
_CTRL
16#0035
53
The format identifier of the
transferred configuration is
invalid
Check the configuration 20, 21
_CTRL
16#0036
54
TSAPs are not unique in the
configuration or exist more
than once
Check the configuration 20, 21
_CTRL
16#0038
56
The configuration is not
unique (IP addresses are
incorrect, neither clients nor
servers are configured,
channel for STEP 7
Micro/WIN 32 not activated)
Check the configuration 20, 21
_CTRL
16#003A
58
The module name for the CP
243-1 was changed in the
configuration.
Check the configuration 20, 21
_CTRL
16#003B
59
The configuration has an
invalid IP address
Check the configuration 20, 21
_CTRL
Summary of Contents for SIMATIC NET CP 243-1
Page 6: ...Preface CP 243 1 6 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 10: ...Table of contents CP 243 1 10 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 104: ...Programming 4 5 ETHx_FTPC CP 243 1 104 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 124: ...Certification CP 243 1 124 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 138: ...Sample program CP 243 1 138 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 142: ...Index CP 243 1 142 Operating Instructions 03 2012 C79000 G8976 C244 02 ...