Diagnostics
5.2 Error messages of the CP 243-1
CP 243-1
110
Operating Instructions, 03/2012, C79000-G8976-C244-02
5.2.1
Error messages in byte format
Error byte
Description
Reaction/remedy
Transfer mechanism
hex
dec
Byte offset in the
SM area
Return value
(ETHx_)
16#01
1
Timeout on the S7 bus
Automatic restart
25 - 32
33
34
35
_XFR
_CFG
_EMAIL
_FTPC
16#02
2
Data access terminated due
to an ABORT command
A new read/write
request can be started
25 - 32
34
35
_XFR
_EMAIL
_FTPC
16#03
3
The transfer parameter
DATA or MAIL or OP is
outside the configured area
Check user program or
configuration
25 - 32
34
35
_XFR
_EMAIL
_FTPC
16#04
4
The connection could not be
set up at the S7 level
The attempt to
establish a connection
is repeated
25 - 32
_XFR
The connection was aborted
or an attempt was made to
execute a read/write
request on a channel that
was not ready
Check connection path
to the communications
partner or configuration
of the communications
partner
25 - 32
_XFR
The connection could not be
established or was aborted
or the e-mail configuration
file on the CP 243-1 was
changed or an attempt was
made to execute a request
and the parameter
assignment for the e-mail
service was not correct.
Check connector of
connection to the
communications
partner
Check .edb file on the
CP 243-1 for
uniqueness and
completeness
34
_EMAIL
The connection could not be
established or was aborted
or the FTP configuration file
on the CP 243-1 was
changed or an attempt was
made to execute a request
and the parameter
assignment of the FTP
client service was not
correct.
Check connector of
connection to the
communications
partner
Check .fdb file on the
CP 243-1 for
uniqueness and
completeness
35
_FTPC
16#05
5
The FTP connection was
aborted
Check connection path
to the communications
partner
Check FTP server
configuration for
completeness
36
Summary of Contents for SIMATIC NET CP 243-1
Page 6: ...Preface CP 243 1 6 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 10: ...Table of contents CP 243 1 10 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 104: ...Programming 4 5 ETHx_FTPC CP 243 1 104 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 124: ...Certification CP 243 1 124 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 138: ...Sample program CP 243 1 138 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 142: ...Index CP 243 1 142 Operating Instructions 03 2012 C79000 G8976 C244 02 ...