Planning the use
3.4 Mounting Positions and Type of Fixation
KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01
33
The following mounting positions are permitted:
ದ
Mounting position
Deviation from the vertical
operating temperature, permissible
①
Inclined
< 30°
0 to 45 °C
②
Vertical
0°
0 to 55 °C
CAUTION
Impermissible ambient temperatures
Do not operate the HMI device without auxiliary ventilation. If the maximum permissible
ambient temperature is exceeded, it may lead to damage. The approvals and warranties for
the HMI device will become void!
If the maximum permissible ambient temperature is exceeded, only operate the HMI device
with auxiliary ventilation.
Type of fixation
Mounting clamps are provided for mounting the device - see chapter "Accessory kit
(Page 14)".
①
Hooks
②
Screws
The main dimensions of the HMI device are not exceed by the installation of the mounting
clamps.