Consider the permitted temperature range for operation that depends on the mounting
position.
Mounting type Ambient temperature for operation
Rail mounting
•
Vertical: 0 to 50 °C
•
Horizontal: 0 to 40 °C
Wall mounting
•
Vertical: 0 to 45 °C
•
Horizontal: 0 to 40 °C
Clearances
Ensure that the following clearances measurements to another component or to a wall of a
housing are complied with:
•
Below the device:
≥
50 mm
•
Above the device:
≥
50 mm