2-1
IM 178-4
C79000-G7076-C178-01
Installing and Removing the Module
Selecting the Location
A horizontal installation is preferable. If you install the module vertically, remember
that the ambient temperature is restricted (max. 40
_
C).
Important Safety Rules
For modules in the S7-300 design, there are important rules that must be kept to.
These rules and regulations are explained in the manual
S7-300 Programmable
Controller, Hardware and Installation, CPU Data.
Rules
When installing the IM 178-4, no particular measures are necessary regarding
electrostatic discharge (ESD).
Required Tools
To install or remove the IM 178-4, you require a 4.5 mm screwdriver.
Installation
To install the IM 178-4 on a rail, follow the steps outlined below. For further
information about installing modules, refer to the manual
S7-300 Programmable
Controller, Hardware and Installation, CPU Data.
1. Hook the IM 178-4 on to the rail and push in the bottom section of the module.
2. Screw the IM 178-4 tight (torque approximately 0.8 to 1.1 Nm).
3. Plug in the front connector and screw it tight.
4. Fit the shield contact element.
The order number of the shield contact element is 6ES7 390-5AA00-0AA0.
5. Plug in the bus connector.
The order number of the bus connector is 6ES7 972-0BA10-0XA0 or
6ES7 972-0BB10-0XA0.