Technical Data
A-4
TP 070 Equipment Manual
Release 03/00
Compliance of the named products with the regulations of Directive 89/336 EEC is
verified by conformance with the following standards:
Noise immunity
Static discharge
(contact discharge/air discharge)
EN 61000–4–2
6 kV/8 kV
RF irradiation
EN 61000–4–3
10 V/m, 80% AM,
1 kHz
Pulse modulation
ENV 50204
900 MHz
"
5 MHz
10 V/meff., 50% ED, 200 Hz
RF conduction
EN 61000–4–6
150 kHz – 80 MHz
10 V, 80% AM, 1 kHz
Burst interference
Supply lines
Process data lines
Signal lines
EN 61000–4–4
2 kV
2 kV
1 kV
Radio interference
Radio interference level complying to
EN 55011
Class A