Mounting
4.3 Fix the device with stainless steel front using clamps
SIMATIC HMI IPC677C
Operating Instructions, 04/2013, A5E02722710-04
39
IP54 degree of protection
The IP54 degree of protection is guaranteed for mounting together with the ring seal.
CAUTION
Observe the panel seal when mounting
Ensure you do not damage the panel seal when mounting the device.
Note
Control cabinet installation: Material strength at the mounting cut-out
Ensure that the material strength at the mounting cut-out is a minimum of 2 mm and a
maximum of 6 mm. Please follow the specifications for the dimensions in the "Preparing the
mounting cut-out" section.
The degrees of protection are only guaranteed when the following is observed:
•
The surface plane deviation of the mounting cut-out in relation to the external dimensions
of the control unit amounts to ≤ 0.5 mm when the control unit is mounted.
4.3
Fix the device with stainless steel front using clamps
Introduction
This section describes how to mount the device in a control panel.
NOTICE
Mount the device as intended. This will avoid damage to the device and loss of warranty.
Follow the installation instructions.
Procedure
1.
Ensure that the seal does not become twisted during mounting, otherwise the mounting
cut-out may not be correctly sealed.
2.
Working from the front, insert the device into the prepared and deburred mounting cut-
out. Take the necessary precautions to ensure the device cannot drop out of the control
panel before it has been secured in place.