Commissioning and Diagnostics
5-27
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
5.5.2
Module interrupts (COM PROFIBUS)
You can assign parameters to diagnostic and hardware interrupts for modules
having analog inputs with COM PROFIBUS.
For
modules with analog outputs
EM 142 DO 4
DC 24V/2A (6ES7 142-1BD40-0XB0)
PM 148 DO 4
DC 24V/2A
BM 143-DESINA and EM 143-DESINA
BM 141 DI 8
DC 24V ECOFAST DIAG
EM 141 DI 8
DC 24V DIAG
it is possible to configure diagnostic interrupts.
The alarms are simulated in the extended diagnosis of the ET 200X (see Section
5.6.9). You can continue processing the interrupt messages in the user program of
the DP master.
5.6
ET 200X diagnostics with STEP 7 and STEP 5
Slave diagnosis
The slave diagnosis behaves in accordance with the IEC 61784-1:2002 Ed1 CP
3/1 standard. Depending on the DP master, It can be read using STEP 7 or
STEP 5 for all DP slaves that comply with the standard.
Displaying and structuring the slave diagnostics is described in the following
sections.
BM 141, BM 141-ECOFAST, BM 142 and BM 143-DESINA provide the slave
diagnosis that complies with the Standard. Note the differences in the diagnostic
frame depending on which version and which release you have.
The basic modules provide an extended diagnosis, depending on the DP master
and the parameterization.
Note
The extended diagnosis can only be used in the slave mode that complies with
the Standard (not in S7 slave operation).
Diagnosis as per the Standard and module diagnosis will always be signaled,
even if no alarm is enabled during parameterization of the basic module.
Summary of Contents for SIMATIC ET 200X
Page 8: ...Preface viii ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 20: ...Contents xx ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 40: ...Product Overview 1 20 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 58: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 80: ...Installation 3 22 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 124: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 328: ...Order Numbers A 10 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 348: ...Dimesioned Drawings and Pinouts C 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 362: ...Index Index 8 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...