Advanced commissioning
7.3 Jogging
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
97
7.3
Jogging
The "Jog" function is typically used to temporarily move a machine part using local control
commands, e.g. a transport conveyor belt.
Commands "Jog 1" or "Jog: 2" switch the motor on and off.
The commands are only active when the inverter is in the "Ready for switching on" state.
Figure 7-4
Behavior of the motor when "jogging"
After switching on, the motor accelerates to the setpoint, jog 1 or setpoint, jog 2. The two
different setpoints can, for example, be assigned to motor clockwise and counter-clockwise
rotation.
When jogging, the same ramp-function generator is active as for the ON/OFF1 command.
Jog settings
Parameter
Description
p1058
Jogging 1 speed setpoint (factory setting 150 rpm)
p1059
Jogging 2 speed setpoint (factory setting -150 rpm)
p1082
Maximum speed (factory setting 1500 rpm)
p1110
Inhibit negative direction
=0: Negative direction of rotation is enabled =1: Negative direction of rotation is
inhibited
p1111
Inhibit positive direction
=0: Positive direction of rotation is enabled =1: Positive direction of rotation is
inhibited
p1113
Setpoint inversion
=0: Setpoint is not inverted
=1: Setpoint is inverted
p1120
Ramp-function generator ramp-up time (factory setting 10 s)
p1121
Ramp-function generator ramp-down time (factory setting 10 s)