10-3
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
10.2 General Technical Specifications
Climatic Environmental Conditions
to IEC 1131-2
Temperature, operation
– 25 ... + 60
°
C
Temperature,
storage/transport
– 40 ... + 70
°
C
Temperature change
Operation
Storage/transport
max. 10
°
C/h
max. 20
°
C/h
Relative humidity
10 ... 100 %
Atmospheric pressure
Operation
Storage/transport
860 ... 1060 hPa
660 ... 1060 hPa
Degree of protection IP to
IEC 529
IP 66 / IP 67
(DI16/DO16 not tested)
Operating conditions with
chemically active
pollutants to IEC 654-4
Class 2
Mechanically Conditions
Operating conditions to
IEC 654-3
10 Hz
v
f < 57 Hz
57 Hz
v
f < 150 Hz
Mode of vibration
Vibration period
Operating conditions
to IEC 654-3
Constant amplitude
0,35 mm
Constant acceleration 5 g
Frequency sweeps with
sweep rate of 1
octave/min.
10 frequency sweeps per
axis in each of the 3 axes
vertical to each other
U.T.1 (corresponds to
100 % frequency)
Shock-tested to
IEC 68-2-27
Type of shock
Shock intensity
Direction of shock
Half sine
30 g peak value,
18 ms duration
6 shocks in each of the 3
axes vertical to each other
Bump test to IEC 68-2-29
Type of shock
Shock intensity
Direction of shock
Half sine
25 g peak value,
6 ms duration
1000 shocks in each of the
3 axes vertical to each
other
Drop and topple to
IEC 68-2-31
Tested with
Height of fall 100 mm
Electromagnetic Compatibility (EMC)/
Noise Immunity
Electrostatic discharge test
to IEC 801-2
Test voltage
Discharge on all parts that
are accessible to the
operator in normal
operation
8 kV air discharge
4 kV relay discharge
(relative humidity 30 to
95 %)
Electromagnetic field test
to IEC 801-3
Field strength 10V/m
Fast transient burst to IEC
801-4
Digital input/output
module
Analog input/output
DC voltage supply
Communications
interface
2 kV
2 kV
2 kV
2 kV
Safety Information
Insulation rating
Between electrically
independent circuits
and circuits connected
to central earthing
point
Between all circuits
and central earthing
point
to DIN VDE 0160
(05.1988)
to DIN VDE 0160
(05.1988)
Radio interference
suppression
to EN 50081-2 for
industrial applications
General Technical Specifications
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...