Functions and Technical Specifications
4-5
EM 148-FC
Frequency Converter
A5E00065321-03
Table 4-4
Structure of the status word, Fortsetzung
Bit
Remarks
Value
Description
2
Operation disabled
0
See control word, bit 3
Operation enabled
1
3
No problems
0
Acknowledgment
required
1
Acknowledgment is required before a restart
following an error (see Section 4.1.3)
4
Control bit 1 = 0
0
Not ready for operation (AUS2)
Control bit 1 = 1
1
Ready for operation
5
Control bit 2 = 0
0
Not ready for operation (AUS3)
Control bit 2 = 1
1
Ready for operation
6
No starting lockout
0
Starting lockout
1
Cancel with bit sequence 1
→
0
→
1 in control
bit 0
7
No warning
0
Warning
1
Drive still in operation, acknowledgment not
required
8
–
x
No meaning
9
On-site operation
0
Control using the hand-held controller
Guidance required
1
Control via programmable controller
10
Under f
0
Converter output frequency is lower than the
setpoint value *.
f reached
1
Converter output frequency is greater or equal
to the setpoint value *.
11
No clockwise
rotation
0
Clockwise rotation
1
Direction of rotation of the motor
12
No
counterclockwise
rotation
0
Counterclockwise
rotation
1
Direction of rotation of the motor
13 to 15
–
x
No meaning
*
This bit is only set if the setpoint value is specified with a minimum resolution of 0.05 Hz.
Summary of Contents for SIMATIC EM 148-FC
Page 56: ...Functions and Technical Specifications 4 22 EM 148 FC Frequency Converter A5E00065321 03 ...
Page 66: ...Mode of Functioning 5 10 EM 148 FC Frequency Converter A5E00065321 03 ...
Page 70: ...Dimensioned Drawing B 2 EM 148 FC Frequency Converter A5E00065321 03 ...
Page 76: ...4 Product Information on Manual EM 148 FC Frequency Converter Edition 04 2003 A5E00476687 03 ...