A field device connected to the service port is automatically detected if it was last in operation
on this CFU PA at one of the other fieldbus ports.
● It is automatically routed (mapped) to the original fieldbus connection of the CFU PA.
● The original fieldbus connection is deactivated when the field device is detected at the
service port until you disconnect the field device from the service port or deactivate the
service port.
● Current and voltage of the field device connected to the service port are not monitored.
Behavior of a field device at the service port
WARNING
Process operation
If the field device is connected to the service port, values for the field device continue to be
transferred to the process.
Make sure that the field device is not used in the process mode at the time of calibration.
Additional information
You can find information on the use of the service interface in the section "CFU PA: Using
service interface (Page 124)".
8.8.3.7
CFU PA: Manual integration of a field device
The CFU PA attempts to read the supported IO from the field device.
If the attempt of the CFU PA to read the IOs from the field device fails, you can manually
connect the field device to the CFU PA.
Note
Manual integration enabled for a fieldbus connection
When manual integration is enabled for a fieldbus connection, the following functions are
disabled for this fieldbus connection:
● Automatic import of the identification numbers (IOs) from the field device by the CFU PA
● Automatic assignment of the identification numbers (IOs) by the CFU PA in the field device
Basic procedure
1. Activate the "Manual field device integration" parameter in HW Config for the fieldbus
connection of the CFU PA.
You can find information on this in section "CFU PA: Assigning parameters to the
PROFIBUS PA Master (parameter overview - FB M) (Page 97)".
2. Set the IO in the field device such that it matches the configuration.
Commissioning
8.8 Commissioning (offline)
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
99
Summary of Contents for Simatic CFU
Page 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...