2AO I HF analog electronic module (6ES7135-4MB02-0AB0)
Manual, 04/2007, A5E01076972-01
13
Parameters
2
2.1
Parameters
Table 2-1
Parameters for analog output module
2AO I HF
Range of values
Default setting
Applicability
Group diagnostics (parameter
assignment error, internal error)
•
Disable
•
Enable
Disable
Module
Diagnostics: Wire break
1
•
Disable
•
Enable
Disable
Channel
Response to CPU/master STOP
•
No output current or
voltage
•
Substitute a value
•
Keep last value
No output current or
voltage
Module
Type/range of output
•
Deactivated
•
4 to 20 mA
•
± 20 mA
4 to 20 mA
Channel
Substitute value
2
To 65,535 (value range must
lie within the nominal range)
± 20 mA: 0 mA
4 mA to 20 mA 4 mA
Channel
1
No diagnostics detection between -1.1852 mA and +1.1852 mA.
2
If there is no voltage being supplied to the interface module or COMPACT module but the supply to the analog output
modules continues, the substitute values that have been assigned parameters are output. Substitute values must be within
the nominal range. You can assign values from -27,648 to +27,648 as parameters (when assigning parameters using the
GSD file).