Analog electronic modules
4.2 Analog value representation
ET 200S
4-10
Manual, Edition 10/2005, A5E00514527-01
Measuring range for thermocouple: Type C
Table 4-15 SIMATIC S7 format: Measuring range Type C in °C and °F
Units
Units
Type C in °C
Decimal Hexadecima
l
Type C in °F
Decimal
Hexadeci
mal
Range
> 2500.0
32767
7FFF
H
> 3276.6
32767
7FFF
H
Overflow
2500.0
:
2315.1
25000
:
23151
61A8
H
:
5A6F
H
3276.6
:
2786.6
32766
:
27866
7FFE
H
:
6CDA
H
Overshoot range
2315.0
:
0.0
23150
:
0
5A6E
H
:
0000
H
2786.5
:
32.0
27865
:
320
6CD9
H
:
0140
H
Rated range
0.1
:
-120.0
-1
:
-1200
FFFF
H
:
FB50
H
31.9
:
-184.0
319
:
-1840
013F
H
:
F8D0
H
Undershoot
range
< -120.0
-32768
8000
H
< -184.0
-32768
8000
H
Underflow
Measuring range for thermocouple type E
Table 4-16 SIMATIC S7 format: Measuring range Type E in °C and °F
Units
Units
Type E in °C
Decimal Hexadecima
l
Type E in °F
Decimal
Hexadeci
mal
Range
> 1200.0
32767
7FFF
H
> 2192.0
32767
7FFF
H
Overflow
1200.0
:
1000.1
12000
:
10001
2EE0
H
:
2711
H
2192.0
:
1832.1
21920
:
18321
55A0
H
:
4791
H
Overshoot range
1000.0
:
-270.0
10000
:
-2700
2710
H
:
F574
H
1832.0
:
-454.0
18320
:
-4540
4790
H
:
EE44
H
Rated range
< -270.0
- 32768
8000
H
< -454.0
- 32768
8000
H
Underflow