10 Calibration
10.4 Calibrating the Measuring Voltage Input of Neutral Conductor VN
207
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
10.4
Calibrating the Measuring Voltage Input of Neutral Conductor VN
10.4.1
Calibrating SICAM MMU (Potential Divider Voltage Measurement)
Measurement Setup
Fig. 10-7
Measurement Setup for Calibrating VN
Measuring Ranges
You can perform the calibration for the following alternating-voltage measuring ranges:
•
AC 63.5 V
•
AC 110 V
•
AC 230 V
•
AC 400 V
Calibration
To calibrate the alternating-voltage measuring ranges, proceed as follows:
✧
Set up the measurement as shown in figure 10-7 or figure 10-10, acc. to device version.
Reference
N
Voltage
Output
SICAM-MMU_7KG9663_US.book Page 207 Monday, December 7, 2015 12:22 PM