7 Operation
7.3 Configuration of the Device
116
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Communication Protocol IEC 60870-5-104
To edit the settings of the Ethernet communication with IEC 60870-5-104 bus protocol, proceed as follows:
✧
In the navigation window, click the
Administrative
menu and then
Communication Ethernet
.
✧
Select the entry
IEC 60870-5-104
from the
Bus protocol
list box.
Fig. 7-37
Configure Tab, Communication Ethernet, Bus Protocol IEC 60870-5-104
✧
Enter the desired values in the fields and select the corresponding parameters using the list boxes and
radio buttons according to table 7-10 on page 114.
✧
After the parameterization click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
Activation
of the device configuration
Activating the Set of Parameters
. If you want to change other settings, enter the
changes and then enable the device configuration as described in section
.
NOTE
Measured values transmitted with the IEC 60870-5-104 protocol are divided into different data groups for the
parameterization. With the selection of the
Measured value data group
, it is determined, for which measured
values the further parameters apply.
To navigate to the page for setting the
measured value data group
, click either the entry
IEC 60870-5-104
page
(see figure 7-37) or select the menu item
IEC 60870-5-104
in the
Administrative
menu. You will find
more information on this topic in the following section
Default Settings and Setting Ranges of the Measured