SICAM FCM Current-Transformer Adapter, Accessory
E50417-X8950-C590-A2, Edition 06.2018
Page 2
SICAM FCM Current-Transformer Adaptor
Manual
s
Figure 1-2 Components of the Current-Transformer Adaptor SICAM FCM
Technical Data
g
1-1 General Characteristics
1-2 Environment
Characteristics
Specifications
Characteristics
Specifications
Rated input current
1 A or 5 A
Operating temperature range
-40 °C to + 70 °C
Accuracy
1 A: ± 1 %
5 A: ± 3 %
Storage temperature range
-40 °C to + 85 °C
Accuracy range
1 A: 0.4 A to 8 A
5 A: 0.4 A to 50 A
Humidity range
0 to 95 %, non-condensing
Frequency
50 Hz/60 Hz
Altitude above sea level
Maximum up to 2000 m
Thermal overload
100 A for 1 s
Rated output
225 mV
Consumption per phase
and ground path
≤ 0.1 VA (at
Ι
N
= 1 A)
≤ 0.5 VA (at
Ι
N
= 5 A)
1-3 Safety
1-4 Dimensions
Characteristics
Specifications
Characteristics
Specifications
Dielectric as per IEC 61010-1 2.5 kV
Dimensions
43 mm x 90 mm x 30 mm
Impulse as per IEC 61010-1
4 kV
Weight
66 g
Vibration as per IEC 60068-2-
6/IEC 60255-21-1
Class II
Inner diameter of CT
5.8 mm