Siemens SICAM FCG Manual Download Page 7

SICAM FCG Device  

6MD2340

  

 

 

 

                     

       

 

 

 

 

 

Product Information  

E50417-X1040-C584-A3, Edition  09.2016 

 

EMC Test for Noise Emission (Type Test) 

 

Standard

  

 

IEC/EN 61000-6-4 

  

Radio noise voltage to lines, 

only auxiliary voltage  
IEC-CISPR 11 

150 kHz to 30 MHz limit class A 

 

Mechanical Stress Tests 
Vibration and Shock Stress during Stationary Operation  

Standards

  

 

IEC 62586-1 and IEC 60068

  

Oscillation  
IEC 62586-1, class II;  
IEC 60068-2-6 test Fc 

Sinusoidal  
10 Hz to 60 Hz: 

±

 0.075 mm 

amplitude; 60 Hz to 150

 

Hz:  

1 g acceleration  
Frequency sweep rate 1 

octave/min 20 cycles in 3 

orthogonal axes. 

Shock  
IEC 62586-1, class II;  
IEC 60068-2-27 test Ea 

Semi-sinusoidal 
5 g acceleration, duration 11 ms, 

each 3 shocks in both directions 

of the 3 axes 

Seismic vibration 
IEC 62586-1, class II; 
IEC 60068-3-3 test Fc 

Sinusoidal 
1 Hz to 8 Hz: 

±

 7.5 mm 

amplitude (horizontal axis)  
1 Hz to 8 Hz: 

±

 3.5 mm 

amplitude (vertical axis) 
8 Hz to 35 Hz: 2 g acceleration 

(horizontal axis)  
8 Hz to 35 Hz: 1 g acceleration 

(vertical axis)  
Frequency sweep 1 octave/min  
1 cycle in 3 orthogonal axes 

 

Vibration and Shock Stress during Transport  

Standards  

 IEC 62586-1 and IEC 60068  

Oscillation  
IEC 62586-1, class 2;  
IEC 60068-2-6 test Fc 

Sinusoidal  
5 Hz to 8 Hz: 

±

 7.5 mm 

amplitude;  
8 Hz to 150 Hz: 2 g acceleration 
Frequency sweep 1 octave/min  
20 cycles in 3 orthogonal axes 

Shock  
IEC 62586-1, class 1;  
IEC 60068-2-27 test Ea 

Semi-sinusoidal 
15 g acceleration,  

duration 11 ms,  
Each 3 shocks (in both directions 

of the 3 axes) 

Shock  
IEC 62586-1, class 1;  
IEC 60068-2-29 test Eb 

Semi-sinusoidal 
10 g acceleration,  

duration 16 ms,  
Each 1000 shocks (in both 

directions of the 3 axes) 

 

Climatic Stress Tests 
Temperatures  

Standards

  

 

IEC 60068

  

Type test (in acc. with IEC 

60068-2-1 and IEC

 

60068-2-2, 

Test bed for 16 h) 

-20 

°

C to +70 

°

C or -4 

°

F to +158 

°

Permissible temporary 

operating temperature (tested 

for 96 h) 

-20 

°

C to +70 

°

C or -4 

°

F to +158 

°

Recommended for permanent 

operation (in acc. with IEC 

60255-6) 

-20 

°

C to +70 

°

C or +14 

°

F to +131 

°

Limit temperatures for storage 

-25 

°

C to +70 

°

C or -13 

°

F to +158 

°

Limit temperatures for transport  -25 

°

C to +70 

°

C or -13 

°

F to +158 

°

Storage and transport with factory packaging 

 
Humidity  

Standards  

 IEC 62586-1 and IEC 60068  

Permissible humidity 

Mean value per year 

 75 % relative 

humidity; on 10

 

days and 40 

°

C of the 

year up to 93 % relative humidity; 

condensation is not allowed. 

Arrange the devices so that they are not exposed to direct sunlight or 

extreme temperature changes. This will prevent condensation in the 

device. 

 
Dimensions 

Mass 

approx. 0.550 kg 

Dimension (W x H x D) 

96 mm x 96 mm x 100 mm 
3.78 in x 3.78 in x 3.94 in 

Summary of Contents for SICAM FCG

Page 1: ...excluded We do not provide any technical support for the Product if it has been modified Notes on Safety This document contains notes that must be adhered to for your own personal safety and to avoid damage to property However it does not constitute a complete description of all safety measures required for installation service and maintenance of the equipment module device in question Details are...

Page 2: ...way that meets the requirements of standard ISO 2248 Check the packing for external transport damage Damaged packing may indicate that the devices inside have also sustained damage Unpack devices carefully do not use force Visually check the devices to ensure that they are in perfect mechanical condition Check the enclosed accessories against the delivery note to make sure that everything is compl...

Page 3: ...ltage and to the maximum values 2 Connect the desired devices to the terminals and plug connectors see figure 1 3 Install the SIM card and connect the GSM antenna according to Device Manual 4 Switch on the connected peripheral devices and the supply voltage of the device NOTE The device does not have a power on off switch Switch on off the supply voltage at the respective isolating device or at th...

Page 4: ...f the device is stored for an extended period of time Siemens recommend to connect the device to the supply voltage for 1 or 2 days once a year to reform the electrolytic capacitors in the device This procedure should also be carried out before operating the device Transport SICAM FCG with 1 contained lithium metal cell button cell with 0 07 g lithium content meets the preconditions of Special Pro...

Page 5: ...nsmission rate 10 100 Mbit s Cable for 100Base T 100 Ω to 150 Ω STP CAT5 Maximum cable length 100Base T 100 m if installed GSM Antenna and Antenna Interface Requirements for Antenna Type Fixed antenna For use in industrial environment acc to EN IEC 61010 1 Ed 3 CAT III Detached antenna For remote installation in residential commercial and light industrial environments EN IEC 61010 1 Ed 3 CAT III A...

Page 6: ...sulation Test Power supply Rated voltage DC 12 or DC 24 V no insulation Ethernet interface Insulation SELV Rated voltage DC 50 V insulation test voltage DC 700 V Rated voltage DC 50 V insulation test voltage AC 1500 V Binary outputs Insulation reinforced CAT III Rated voltage 300 V Insulation test voltage AC 3 51 kV Binary inputs Insulation reinforced CAT III Rated voltage Block P 300 V Rated volt...

Page 7: ... 5 Hz to 8 Hz 7 5 mm amplitude 8 Hz to 150 Hz 2 g acceleration Frequency sweep 1 octave min 20 cycles in 3 orthogonal axes Shock IEC 62586 1 class 1 IEC 60068 2 27 test Ea Semi sinusoidal 15 g acceleration duration 11 ms Each 3 shocks in both directions of the 3 axes Shock IEC 62586 1 class 1 IEC 60068 2 29 test Eb Semi sinusoidal 10 g acceleration duration 16 ms Each 1000 shocks in both direction...

Page 8: ...s Product Information E50417 X1040 C584 A3 Edition 09 2016 1 SICAM FCG Terminal Side 2 SICAM FCG DIN Rail Side 3 SICAM FCG Device Top Side Cover of Battery Compartment 4 SICAM FCG DIN rail Assembly 5 SICAM FCG Dimension Drawing ...

Reviews: