Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC
143
DC8-001-2.09, Edition 08.2016
If for security reasons no connection between the networks may be established, the use of a
second IP address on interface X4 can be suppressed. Thereto, in the initial parameterization
can be defined whether the parameter
Mode of ethernet ports
is permanently displayed
or hidden.
This can be adjusted with the expert parameter
Advanced parameters | Parameter |
“Mode of ethernet ports“
using the following selection:
•
display (selection)
(default)
•
hide (freeze)
Note
With the selection
hide (freeze)
this parameter and the parameter
Mode of ethernet ports
are per-
manently hidden. A further change of these parameters is no longer possible!
The set mode remains unchanged, unless the target device will be restarted via a complete
reparameterization:
•
Initialization with other parameters or with an anew generated SD card (SICAM TOOLBOX II).
•
Initialization with an empty SD card (SICAM WEB).
•
Store the changed settings by clicking
The stored values require a restart of the target device and are only active after the startup.
Note
After each change of the data, the target device can be accessed only by selection of the newly set IP ad-
dress(es).
If the access to the web server is no longer possible, check the IP settings of the engineering PC.
5.1.2.4.1 Access Options for the Engineering PC in Operation
DHCP service
used
DHCP server
available
Access option
IP address
SICAM CMIC
IP address engineering
PC
Autoconfigu-
ration
=
NO
Irrelevant
Ethernet (X1)
Own IP address
=
<set value>
<free address in subnet of
SICAM CMIC>
Autoconfigu-
ration
=
YES
Yes
Ethernet (X1)
Own IP address
=
<automatic>
assigned by DHCP-
server, if DHCP is ena-
bled on the PC
Autoconfigu-
ration
=
YES
No
Ethernet (X1)
Own IP address
=
<169.254.0.1>
<free address in subnet
169.254.0>
(IP address in
SICAM CMIC is not rout-
ed)
Irrelevant
Irrelevant
Ethernet (X4)
Own IP address
(X4)
=
<set value>
<free address in subnet of
SICAM CMIC>
*)
Irrelevant
Irrelevant
Point-to-Point
(X2)
172.16.0.1
172.16.0.2
(assigned by
SICAM CMIC)
*)
applies only if
Mode of the Ethernet ports
=
2 IP addresses (independent ports)
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...