Installation
74
SICAM RTUs, SICAM AK 3 User Manual
Edition 07.2016, DC2-028-2.03
1.8
Wiring Process Peripherals
1.8.1 General
The process peripherals are connected with the system by means of prefabricated peripheral
cables.
Designation
Item-Number/MLFB
CM-2890 Periphery cable Crimp 5 m
100 pins
TC2-890
6MF13131CJ000AA0
1.8.2
Fitting
Peripheral
Cable
Caution
The peripheral modules must
NOT
be installed in the board rack during the fitting of the associated pe-
ripheral cable.
The fitting is carried out by engaging the peripheral cable in the seating frame.
Proceed as follows:
•
Insert the peripheral cable into the board rack from below, until the point of the grip flap is
fixed between profile rail and seating frame
•
; In the case of wall mounting a plate on the
wall bracket serves as a guide during installation.
1
Guide plate
of rear cover
Profile rail
Seating frame
Point of
grip flap