16 Storage and Transport
Storage
Store the device in a dry and clean location. The
temperature range for storing the device or any of its
replacement modules is -25 °C to +70 °C (-13 °F to
+158 °F).
The relative air humidity must not lead to condensation
or ice formation.
To avoid premature aging of the electrolytic capacitors,
store the device within the recommended temperature
range of +10 °C to +35 °C (+50 °F to +95 °F).
If the device is stored for an extended period of time,
Siemens recommend to connect the device to the
supply voltage for 1 or 2 days once a year to reform the
electrolytic capacitors in the device. This procedure
should also be carried out before operating the device.
In this context, pay attention to the commissioning
notes in Chapter 8.
The Lithium-batteries in our equipment are subject to
Special Provision 188 of the UN Recommendations on
the Transport of Dangerous Goods Model Regulations
and Special Provision A45 of the IATA Dangerous
Goods Regulation and the ICAO Technical
Instructions. This is only valid for the original battery or
original spare batteries.
Transport
If devices are to be shipped elsewhere, you can reuse
the transport packaging. When using different
packaging, you must ensure that the transport
requirements according to ISO 2248 are adhered to.
The storage packing of the individual devices is not
adequade for transport purposes.