14 Operating Parameters
14.1 Process Connections
244
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
14.1
Process Connections
The following process connections are available:
•
•
•
14.1.1
AC Measurement
Parameter
Default Settings
Setting Range
Rated frequency
50 Hz
50 Hz (± 7.5 Hz)
60 Hz (± 9 Hz)
Network type
Four-wire, 3-phase,
unbalanced
1-phase network
Three-wire, 3-phase balanced
Three-wire, 3-phase, unbalanced (2 * I)
Three-wire, 3-phase, unbalanced (3 * I)
Four-wire, 3-phase, balanced
Four-wire, 3-phase, unbalanced
Primary nominal voltage
AC 400.00 V
AC 1 V to AC 1 000 000 V,
dependent on the setting range in the se-
lected network type
Voltage transformer
no
yes
no
At voltage transformer: yes
Primary rated voltage
Secondary rated voltage
AC 400.00 V
AC 400.00 V
AC 100.00 V to 1 000 000.00 V
AC 1.0 V to 1000.0 V
Voltage measurement range
ph-N: AC 400 V
(inject a maximum of
AC 347 V for UL),
ph-ph: AC 690 V
(inject a maximum of
AC 600 V for UL)
ph-N: AC 63.5 V, ph-ph: AC 110 V
ph-N: AC 110 V, ph-ph: AC 190 V
ph-N: AC 230 V, ph-ph: AC 400 V
ph-N: AC 400 V (max. 347 V for UL)
ph-ph: AC 690 V (max. 600 V for UL)
Current measurement range
AC 5 A
AC 1 A
AC 5 A
Current transformer
no
yes
no
At current transformer: yes
Primary rated current
Secondary rated current
AC 1000.00 A
AC 1.00 A
AC 1.00 A to 100 000.00 A
AC 0.01 A to 10.00 A
Zero point suppression
0.3 % (from Vrated, Irated)
0.0 % to 10.0 %
Voltage harmonic unit
%
%
V