7 Operation at Use of a PC
7.3 Configuration of the Device
154
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Ethernet Communication with Bus Protocol Modbus TCP
✧
In the
Bus protocol
list box select the entry
Modbus TCP
.
✧
Enter the desired values in the fields and select the parameters in the list boxes and in the option field as
described in Table 7-18.
✧
After the parameterization click
Send
.
After clicking
Send
, the parameters are transmitted to the device but not enabled yet (passive set of
parameters).
✧
If you do not want to make any additional settings, continue with the
Activation
of the device configuration
Activating the Set of Parameters
. If you want to change other settings, enter the
changes and then enable the device configuration as described in section
.
NOTE
If you have selected
no
under
Use a user-port number
, you can adjust only the
Access rights for user
port 502
, the
Keep Alive time
and the
Communication supervision time
parameters.
NOTE
After changing the network settings and subsequent parameter activation the device will reset.