7 Operation at Use of a PC
7.3 Configuration of the Device
151
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.6.2 Communication Ethernet
Default Settings and Setting Ranges of the Communication Ethernet
1)
After the parameter changes have been enabled, the device will reset.
2)
After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later reopen these connections.
Table 7-18
Communication Ethernet Settings
Parameter
Default Setting
Setting Range
IP address
1)
192.168.0.55
Any
0.0.0.0 = DHCP
Subnet mask
1)
255.255.255.0
Any
Default gateway
1)
192.168.0.1
Any
Enable SNMP
no
no
yes
Bus protocol
Modbus TCP
-none-
Modbus TCP
Bus Protocol Modbus TCP
Use a user-port number
2)
no
no
yes
User-port number
2)
(can only be set when
Use a user-port
number
is parameterized with
yes
)
10000
10000 to 65535
Access rights for user port
(can only be set when
Use a user-port
number
is parameterized with
yes
)
Full
Full
Read only
Access rights for port 502
Full
Full
Read only
Keep Alive time
10 s
0 s = switch off
1 s to 65 535 s
Communication supervision time
600 * 100 ms
0 s = none
100 ms to 6 553 400 ms