Appendix
A.3 MODBUS
SENTRON PAC4200
230
Manual, 09/2008, A5E02316180B-01
Offset
Number
of
registers
Name
Format
Unit
Value range
Access
Byte 2
Port
Byte 2
0 ... 11
Byte 3
Bit
50241
2
Universal Counter DI Count
Signal
Unsigned long
-
Byte 3
0 ... 7
RW
0 = Normal
50243
2
Current Direction a
Unsigned long
-
1 = Inverted
RW
0 = Normal
50245
2
Current Direction b
Unsigned long
-
1 = Inverted
RW
0 = Normal
50247
2
Current Direction c
Unsigned long
-
1 = Inverted
RW
50249
2
Measuring Threshold
Operating Hours Counter
Unsigned long
%
0 ... 10
RW
61167
7
Digital Input Parameters
stInputPara
-
uchar
RW
61175
7
Digital Output Parameters
stOutputPara
-
uchar
RW
62101
8
Event Recording
Parameters
stEventPara
-
uchar
RW
62301
27
Logically Combined Limit
Parameters
stCombLimitPara -
-
RW
1)
Subperiods 0 and 1: Fixed block method; subperiods 0 to 5: Rolling block method
2)
More information is given in the chapter under the also-see link.
See also
Value range for limit source (Page 230)
A.3.13
Value range for limit source
Assignment of the value range 0 to 240 for the Limit x Source parameter
Table A- 21 Assignment of the values 0 to 240
Value
Assignment
0 =
Voltage a-n
1 =
Voltage b-n
2 =
Voltage c-n
3 =
Voltage a-b
4 =
Voltage b-c
5 =
Voltage c-a
6 =
Current a
7 =
Current b
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...