Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
179
P11
Designation on
ATC display
Description
Unit
De-
fault
Range
P11.14 AUTO TEST
TIME
TEST duration
– Duration of the periodic test in minutes.
min
10
1-600
P11.15 AUTO TEST
WITH LOAD
Automatic TEST with load transfer
– Load management during performance of the periodic test:
OFF = The load is not transferred.
Load = Enables load transfer from the network to the generator.
Dummy load = Load simulation is activated; the system load is not
transferred.
OFF OFF
Load
Dummy
load
9.4.12
P12 - Digital Inputs
This menu is divided into 20 sections. These refer to 8 possible digital inputs INP1…INP8
that can be managed directly by the ATC6500, and a further 12 inputs that can be managed
by the ATC6500 via the expansion modules.
P12
Designation on ATC
display
Description
Unit
Default Range
P12.n.01 INPUT FUNCTION
Function of the input INPn
– Selects the function of the selected input (see
table "Functions of the programmable inputs" in
chapter Digital inputs INPx (Page 145))
(misc.) (See Table:
(Page 145))
P12.n.02 CHANNEL NO.
Function index (x)
- Index that is possibly assigned to the function
programmed in the previous parameter. Example: If
the input function is set to Cxx Commands menu
execution, and this input is to perform command
C07 in the Commands menu, then P12.n.02 must
be set to the value 7.
OFF
OFF / 1-99
P12.n.03 CONTACT TYPE
Contact type
– Select the contact type: NO (normally open) or
NC (normally closed)
NO
NO/NC
P12.n.04 DELAY ON
Closing delay
– Contact closing delay for selected input.
s
0.05
0.00-600.00
P12.n.05 DELAY OFF
Opening delay
– Contact opening delay for selected input
s
0.05
0.00-600.00