Operation
8.2 Inputs and outputs of the ATC6500
3KC ATC6500 transfer control device
150
Manual, 05/2019, L1V30538268002A-01
Some functions require another numeric parameter. This is specified by parameters by
means of an index.
Note
Use of an index
An index is used if additional functions are to be used as a source for the output.
For example, an output can function as a source for a counter or for a user alarm.
On replacement or subsequent modification of the modules, attention must be paid to the
addressing (see chapter Addressing of the expansion modules with digital inputs/outputs
(Page 152)).
8.2.5
Table of functions of the digital outputs
The table below lists all functions that can be assigned to the programmable digital outputs
OUTx.
Function
Designation on the ATC6500 Description
Disabled
Disabled
Output disabled
Configurable
Configurable
Free configuration by the user.
Close Source 1 contactor/breaker L1 close
Command to close the contactor/breaker of Source 1.
Open Source 1 contactor/breaker L1 open
Command to open the breaker of Source 1 with possi-
ble spring load.
Close Source 2 contactor/breaker L2 close
Command to close the contactor/breaker of Source 2.
Open Source 2 contactor/breaker L2 open
Command to open the breaker of Source 2 with possi-
ble spring load.
Open Source 1 and Source 2
L1-L2 open
Open both breakers / neutral position of the transfer
switching equipment with motor operator.
Undervoltage release breaker 1
Min V coil 1
Controls the undervoltage release by opening break-
er 1 before the spring load cycle.
Undervoltage release breaker 2
Min V coil 2
Controls the undervoltage release by opening break-
er 2 before the spring load cycle.
Control Generator 1
Start generator 1
Control of the Start / Stop remote control of the gen-
erator on Source 1.
Control Generator 2
Start generator 2
Control of the Start / Stop remote control of the gen-
erator on Source 2.
ATC ready
ATC ready
ATC in automatic mode, without alarms, ready to
switch.
Global alarm A
Global alarm A
Output enabled in the presence of any alarm with the
property "Global alarm A"
Global alarm B
Global alarm B
Output enabled in the presence of any alarm with the
property "Global alarm B"
Source 1 voltage status
SRC1 VOLTAGE OK
This output is enabled if all conditions for the connec-
tion of the load to Source 1 have been met.
Source 2 status
SRC2 VOLTAGE OK
This output is enabled if all conditions for the connec-
tion of the load to Source 2 have been met.