Commissioning
5.2 Setting expansion module parameters
PAC 4DI/2DO expansion module
24
Manual, 11/2018, L1V30545465B-01
Selection
Range
Factory
default setting
MODE
(only with PULSE
INPUT)
Counting of pulses or edges.
•
PULSE:
Pulses are counted.
•
EDGE:
Edges are counted.
PULSE
PULSES PER UNIT
(only with PULSE
INPUT)
Number of pulses that must be received per unit in order
for the counter to be incremented by "1". The reference
unit is defined in the "UNIT" field.
•
1
…
999
1
UNIT
(only with PULSE
INPUT)
Unit to be counted when counting the pulses or edges
received:
•
kWh (active energy)
•
kvarh (reactive energy)
•
"TEXT"
"TEXT" stands for a user-definable unit, e.g. m
3
/h or
pieces. The text sequence used to name the unit must
be defined via the communication interface. The de-
fined text sequence is displayed in the "TEXT" field
when you select "TEXT".
TEXT
(only with PULSE
INPUT
→ TEXT)
Text sequence used to name the unit to be counted.
See "UNIT" field.
TARGET
You will find more detailed information in the following
table.
RELATED COUNTER The associated user-defined pulse counter is displayed
here independently of the action selected.
This function is only available if at least one
SENTRON PAC 4DI/2DO expansion module is plugged
into the SENTRON PAC.