Module
2.5 Configuring
2.5.4.3
Reading all I/O statuses
Send the "rall" SMS to the module to query the statuses of all I/Os.
The module responds with the "<module name> IO status:DO1=x (to) DO4=xUI1=xxx (to)
UI8=xxx" SMS.
UI is replaced with the set input type: AI or DI.
To send the complete IO status to an email address, send the "rall<email>" SMS to the
module.
2.5.4.4
Linking several GSM alarm modules
It is possible to link several GSM alarm modules by SMS.
You can send previously defined messages to other modules by selecting "Send only user
defined text" in the IO configuration.
Example: digital input 8 sends WDO21 on a rising flank to a second unit. This unit receives
the message, switches the digital output 2 and sends a WDO31 message to a third unit, and
so forth. On the falling flank of the first unit, it sends WDO20 to deactivate the digital output
on the second unit and so forth.
It is also possible to send an SMS to the sending GSM alarm module to thus activate digital
outputs in response to digital inputs.
Note
The digital outputs cannot send any messages.