3WA Air Circuit Breaker Communication
System Manual, 11/2021, 92310000004-02
35
Modbus TCP
5
5.1
General
The COM190 communication module supports the Modbus TCP protocol of the Modbus
Organization, described in the following specifications:
•
Modbus Application Protocol V1.1b3
•
Modbus Messaging Implementation Guide V1.0b
You can find more information on the Internet (
).
5.2
Addressing
With Modbus TCP, the COM190 module is addressed via its IP address.
The COM190 has a data point that contains the communication parameters for access via
TCP/IP (IPv4 suite).
Read and write access
Read access to the data point takes place as follows:
•
For the COM190 with role A, via Modbus register number 42009 (hex: 0xA419)
•
For the COM190 with role B, via Modbus register number 43009 (hex: 0xA801)
Write access to the IPv4 suite takes place via a command with Modbus function code 16
(hex: 0x10):
•
For the COM190 with role A, via Modbus register number 42900 (hex: 0xA794)
•
For the COM190 with role B, via Modbus register number 43900 (hex: 0xAB7C)
Modbus TCP port
The default TCP port for a Modbus TCP server is 502. The COM190 module has a data point
"Modbus TCP port" that is configured as 502 in the as-delivered state.
It is possible to change this value. You can find more information in Chapter Configurable
Modbus TCP port (Page 43).